RTR-B124 Room temperature controller, mechanical (heating)
Setpoint range +5...+30 °C, hysteresis 0.5 K
Switching element: bimetal, contact 10 (4) A, 230 V AC
Dimensions 79 x 81 x 26 mm. Input for depression -5K
Setpoint range +5...+30 °C, hysteresis 0.5 K
Switching element: bimetal, contact 10 (4) A, 230 V AC
Dimensions 79 x 81 x 26 mm. Input for depression -5K
RTR-B is a series of one-stage mechanical room thermostats for wall mounting.
The bimetal measuring element activates the switching contact when temperature exceeds the setpoint. The setpoint is set either inside of the housing or with a knob on the front of the device.
Thermostats are designed for use in standard environment. They do not require maintenance and can be installed in any position. Make sure that proper air circulation through the apertures is maintained. Fix the device with 2 or 4 screws on a 50 mm flush-mounted box or any flat surface. In the bottom there is an aperture for cable installation.
The RTR-B124 has a terminal for externally forced temperature drop by –5 K which may be used for night depression. Connect the time scheduler to terminal 5 and apply 230 V AC during the depression time.
Note that the RTRB7... should not be used for both heating and cooling at the same period because of no dead zone between the heating and cooling mode.